CON3000 Conductivity/ Resistivity/ Salinity Transmitter

CON3000 Conductivity/ Resistivity/ Salinity Transmitter

The CON3000 is a full-featured Conductivity or Resistivity or Salinity controller. Simply power up your CON3000 with 110-240V AC power and you get a controller with a wide range of useful features:

2 relays, 1 wash control, 2 each 4-20mA outputs (Cond & Temp or Resistivity & Temp or Salinity & Temp).

Calibration is simple with preset standard and can be pass­word protected with a programmable security code.

Mounting choices include: wall, panel or pipe with all fit­tings included.

The large multi-segmented LCD includes a backlight so it can be easily viewed in all areas.

-     2 each Voltage isolated (500 V) 4-20mA Outputs (Conductivity or Resistivity or Salnity and Temperature)

-     2 Adjustable Hi'Lo Relay/Contacts

-     Large segmented display indicates Conducivity or Resistivity or Salinity and Temperature simultaneously

-     NEMA 4X, IP65 enclosure

-     Programmable wash feature

 

Specifications:

1)     Measuring Range (Conductivity)

0.000 uS/cm -200.0 mS/cm in 6 ranges 0.001 uS/cm resolution, +/-1% Accuracy (Resisitivity) 0.00-20.00 MΩ/cm, 0.01 MΩ/cm resolution, +/-1% Accuracy (Salinity) 0.0 -70.0ppt, 0.1ppt resolution, +/-1% Accuracy

2)     Temperature Range

-30 °C to 130 ° C , 0.1 ° C resolution, 0.2 °C accuracy

3)     Calibration Mode

Any tech & NIST buffers up to 2 points

4)     Cell Constants

0.01, 0.1, 0.7, 10/cm fixed or freely selectable 0.0050 - 19.99/cm

5)     Analog Output 1

0/4 -20mA , corresponding to pH or ORP output. Max load 500 Ω.

6)     Analog Output 2

0/4 -20mA , corresponding to temperature output. Max load 500 Ω

7)     Voltage Output

DC +/- 12V

8)     Set-Points

Contact : 240V AC, 0.5A max Activate: 2 setpoints Hi/Low, On/Off

9)     Enclosure

NEMA 4X IP65, with push-button control pad. HWD: 144 mm (5.67") x 144 mm (5.67") x 115mm (4.53")

10)  Panel Cut-Out

138mm (5.43") x 138mm (5.43")

11)  Weight

approx. 0.80kg (1.75lb)

12)  Mounting Options

Panel, Wall or pipe mount

13)  Ambient Temperature

0 ° C to 50 ° C

14)  Storage Temperature

-20 ° C to 70 ° C

15)  Temperature Compensation

NTC 30K or Pt1000 RTD with automatic compensation or manual

16)  Temperature Coeffcient

Linear comp 0.00-20.00%, Non-linear comp for natural waters

17)  Power Requirement

100-240V AC +/- 10%, 50/60 Hz

18)  Certification

CE

 

 

Documentation:

CON3000 Datasheet